Model: APC Smart-UPS 3000 RM DL3 230V
Connect options:
screen /dev/ttyUSB0 2400
Login credentials: (check bitwarden)
Some tips:
This model seems to use custom SNMP attributes. For example to get temperature run:
snmpget -v1 -c public 172.23.200.1 .1.3.6.1.4.1.318.1.1.1.2.2.2.0
This one doesn't support network access because the only Ethernet port is actually for serial connection.
Eaton Powerware 5125 in the server room. Network interface manualuser_guide.pdf
The batteries of the 6 have been manufactured 2019-03, and installed by Rasmus and Erki Aas in 2019-10.
Last battery swap 2024-08
Erki Aas and past interns have hooked them up to an isolated VLAN for monitoring. There's also an effort to hook them up to a kill-switch, in case of a fire.
This UPS supports on SNMP standard RFC1268 and Eaton proprietary PowerMIB attributes.
Interface default passwords:
To (re)configure allowed SNMP endpoints either use serial or when connected via telnet
execute config_menu
and follow the interactive menu.
+============================================================================+
| [ Main Menu ] |
+============================================================================+
1. Card Settings
2. Reset Card's Configuration to Default
3. Restart Card
4. Locate Card
0. Exit
Please Enter Your Choice => 1
+============================================================================+
| [ Card Settings ] |
+============================================================================+
1. Network Settings
2. Security Settings
3. SNMP and Host Table Settings
4. Quick Status
0. Return to Previous Menu
Please Enter Your Choice => 3
+============================================================================+
| [ SNMP and Host Table Settings ] |
+============================================================================+
1. SNMP MIB/Trap Settings
2. SNMP Trap Receivers Table
0. Return to Previous Menu
Please Enter Your Choice => 2
+============================================================================+
| [ SNMP Trap Receivers Table ] |
+============================================================================+
| IP Address Trap Level MIB Group |
+--Permanent-----------------------------------------------------------------+
+--Dynamic-------------------------------------------------------------------+
+============================================================================+
-----COMMANDS-----------------------------------------------------------------
1. Create - Create a Permanent Trap Receiver Table Entry
2. Modify - Edit a Trap Receiver Table Entry
3. Delete - Delete a Trap Receiver Table Entry
4. Promote - Promote a Dynamic Host to Permanent Entry
0. Return to Previous Menu
Please Enter Your Choice => 1
Enter Receiver IP Address [0.0.0.0] : 172.21.0.6
Select Trap Level [All Traps]
1. None
2. Critical
3. Major
4. Minor
5. All Traps
Please Enter Your Choice => 5
Select MIB Type [PowerMIB]
1. RFC 1628
2. PowerMIB
Please Enter Your Choice => 2
+============================================================================+
| [ SNMP Trap Receivers Table ] |
+============================================================================+
| IP Address Trap Level MIB Group |
+--Permanent-----------------------------------------------------------------+
1) 172.21.0.6 All Traps PowerMIB
+--Dynamic-------------------------------------------------------------------+
+============================================================================+
-----COMMANDS-----------------------------------------------------------------
1. Create - Create a Permanent Trap Receiver Table Entry
2. Modify - Edit a Trap Receiver Table Entry
3. Delete - Delete a Trap Receiver Table Entry
4. Promote - Promote a Dynamic Host to Permanent Entry
0. Return to Previous Menu
Please Enter Your Choice => 0